Current Transformer Test Set Manufacturer,Supplier and Exporter in India

Image Not Found .

Product Code : EL-DSO-10317
Jlab Export is a leading Current Transformer Test Set Manufacturer,and suppliers in India

Current Transformer Test Set (code EL-DSO-10317) is a test set for current transformers with 1 A or 5 A secondaries on 50 Hz systems. Ratio error and phase error are read directly from its LCD, and a current injection set and knee-point voltage equipment form part of the set. JLab (Jain Laboratory Instruments Pvt Ltd, Ambala, India) supplies it to schools, colleges and dealers.

Specifications

ParameterDetail
CTs testedSecondary rated 5 A, for use on 50 Hz; secondary current selector 1 A or 5 A
MeasurementsRatio error and phase error, with automatic and manual facilities; magnetising curve and knee-point voltage of protective CTs
DisplayLCD, direct reading: ratio error in percent, phase error in minutes; LED indication
Phase error range0–1000 minutes
Input current0.05 A to 7.5 A AC
Current range selection1 A and 5 A AC
Accuracy±1% of reading
BurdenOn the standard transformer 1.5 VA at unity power factor; on the ‘X’ transformer, the burden connected externally at the ‘X’ burden terminal + 1.5 VA
TerminalsSeparate terminals for the standard CT and test (‘X’) CT secondaries; burden box terminals on both the standard and the CT under test
ControlsRange selecting switch, aux. ON/OFF switch, hold key; null detector with sensitivity control; ammeter showing the injected current in percentage
IndicationsReverse polarity; ‘Std’ CT secondary open; ‘X’ CT secondary open; high imbalance between the ‘Std’ and ‘X’ CT ratios; over current; ratio error polarity; phase lag/lead; phase error over range
Current injection setVariable output current, 100 A, with digital current meter
Knee-point voltage checkVariac, 2 A, closed type (1 no.); digital multimeters (2 nos.)
Other itemsCurrent meter and timer; CT 100:5 A (2 nos.); CT 100:5 A for the magnetising curve
BuildCompact and light in weight
Quality checkEach test set is visually inspected before dispatch
Pack quantityEach (sold individually)
Minimum order quantity10 units
Dispatch timeUsually 7–10 working days
Product codeEL-DSO-10317
Supplied byJain Laboratory Instruments Pvt Ltd (JLab), Ambala, India

What Is the Current Transformer Test Set Used For?

A current transformer steps a large primary current down to a standard secondary current for meters and relays, and no CT does this perfectly: its secondary current differs slightly in size from the nominal ratio (ratio error) and is slightly shifted in time (phase error). The set measures both by running the CT under test and a standard CT on the same primary current and comparing their secondaries.

Frequently Asked Questions

What is the knee-point voltage of a CT?
It is the point on the magnetising curve where the core starts to saturate, commonly defined as the voltage at which a further 10% rise in secondary voltage needs a 50% rise in exciting current. A protective CT must have a knee point high enough to stay out of saturation at the fault currents its relay has to see.

Why is the phase error shown in minutes?
The angle between the primary and secondary currents of a good CT is very small, so it is quoted in minutes of arc — sixtieths of a degree — rather than in degrees.

What does the null detector do?
It shows when the comparison between the standard and the test CT is balanced. The sensitivity control sets how finely that balance can be read, which matters when the errors are small fractions of a percent.

What information is needed for an export quotation?
Send the number of test sets, the destination country and port or city, your preferred delivery terms (for example FOB or CIF), any packing or labelling requirements, and a tender reference if one applies.

Who supplies this test set?
Jain Laboratory Instruments Pvt Ltd, trading as JLab, of Ambala, Haryana, supplies it and quotes for it directly to colleges, dealers and importers.

Supplier

JLab is the trading name of Jain Laboratory Instruments Pvt Ltd, a laboratory equipment company in India, incorporated in 2017 and based on Hargolal Road, Ambala, Haryana. JLab supplies this CT test set alongside its own electrical and electronics lab equipment, so a protection or measurements lab can put the test set, relay kits and trainers on one enquiry. JLab exports worldwide and ships to buyers in every region — for example Sweden in Northern Europe, Vietnam in Southeast Asia, Uruguay in South America, Hungary in Eastern Europe and Mexico in North America. Tender information is on the JLab lab tenders page.

Related Protection Test Kits and Trainers

More equipment is in the Electronics Lab Equipments range.

Request a Quote

Start an enquiry with the Add To Cart button, or send the number of test sets and the delivery city or port through the contact page.

Last updated: 22 October 2026


   