Basic Refrigeration Training Unit

Product Code : EL-TWL-13135
Jlab Export is a leading Basic Refrigeration Training Unit Manufacturer,and suppliers in India

Domestic refrigerators, freezers, self-contained air conditioners and reverse cycle heat pumps can all be demonstrated on this basic refrigeration training unit. A 1/3 HP hermetic reciprocating compressor runs it on R-134a, and colour-coded hand valves bypass components or change it from cooling to heating. Sight glass tubes at the evaporator and condenser show the refrigerant and oil inside.

Specifications

Compressor 1/3 HP hermetic reciprocating
Refrigerant R-134a
Power supply 220–240 V, 50 Hz
Metering devices Capillary tube, automatic expansion valve, thermostatic expansion valve
Sight glasses Tie-bolt sight glass tubes at the inlet and outlet of the evaporator and condenser
Heat exchangers Indoor and outdoor coils with variable fan speed, drip pan with drain under each
Valves and gauges Colour coded, with pressure gauges at each point of pressure change and hand valves for bypass and heating changeover
Construction Metal frame and panels, steel reinforced component shelf
Supplied with Instructor booklet with lab manual, instructor guide and operation guide, manifold service kit
Minimum order quantity 1 unit
Dispatch time Usually 14–18 working days
Manufacturer JLab (Jain Laboratory Instruments Pvt Ltd), Ambala, India

Lab Exercises on the Training Unit

Most courses start with the basic cycle on the capillary tube. Students read the gauge at each point and watch the sight glasses: vapour enters the condenser, liquid leaves it, and the liquid boils off in the evaporator. They measure the coil temperatures to work out superheat and subcooling. A Handheld Anemometer Digital held at each coil gives the air velocity, so students can relate fan speed to pressure and capacity.

With the hand valves, students then switch the metering device to the automatic expansion valve and the thermostatic expansion valve. They change fan speed to vary the load and note that the automatic valve holds evaporator pressure while the thermostatic valve holds superheat. Later sessions cover heating mode, where the indoor coil becomes the condenser. Service work follows: evacuating with one of the Small Vacuum Pumps and charging through Manifold Gauges For Refrigeration Systems.

Frequently Asked Questions

Which systems can the unit demonstrate?
Domestic refrigerators, freezers, self-contained air conditioning units and reverse cycle or heat pump systems. Colour-coded hand valves bypass parts of the circuit and change it from cooling to heating.

Why does it have three metering devices?
So students can compare them on one circuit. A capillary tube is a fixed restriction, an automatic expansion valve holds evaporator pressure and a thermostatic expansion valve holds superheat. Each responds differently when the load changes.

What can be seen through the sight glasses?
The condition of the refrigerant and oil at the inlet and outlet of the evaporator and the condenser. Students compare what they see in each mode of operation and match it to the gauge readings.

Which compressor and refrigerant does it use?
A 1/3 HP hermetic reciprocating compressor running on R-134a from a 220–240 V, 50 Hz supply. Pressure gauges sit at each point where the pressure is likely to change.

How does it compare with the commercial training unit?
This unit covers domestic and air conditioning cycles with a hermetic compressor. The Dual-Application Commercial Refrigeration Training Unit uses a 1/2 HP semi-hermetic compressor with low and medium temperature evaporators, a defrost timer and refrigerant flow meters.