Water Cooling Tower Apparatus

Product Code : EL-TL-10060
Jlab Export is a leading Water Cooling Tower Apparatus Manufacturer,and suppliers in India

Water Cooling Tower Apparatus (code EL-TL-10060) is a forced draught, counter flow cooling tower in which water heated by a 3 kW geyser falls over wire mesh packing while a 1 HP centrifugal blower drives air up through it. Students use it to study tower operation and work out the energy balance. JLab makes this cooling tower trainer in Ambala, India.

Specifications

ParameterDetail
TowerForced draught, counter flow; M.S. sheet, 200 x 200 mm cross-section, 1.2 m height, acrylic front
PackingWire mesh
Hot waterGeyser, 3 kW
Air supplyCentrifugal blower, 1 HP
Water flow measurementRotameter at the inlet; measuring tank at the outlet
Air flow measurementCalibrated orifice with water manometer
TemperaturesMultichannel digital temperature indicator; dry and wet bulb air temperatures at 5 intermediate stations
FinishAnti-corrosion powder coating
Services required440 V, 32 A AC with neutral and earthing; water 10 litre/min at constant head; floor space about 2 m x 1.5 m
DocumentationTechnical manual
Quality checkEach cooling tower is visually inspected before dispatch
Pack quantityEach (sold individually)
Minimum order quantity1 unit
Dispatch timeUsually 14–18 working days
Product codeEL-TL-10060
ManufacturerJain Laboratory Instruments Pvt Ltd (JLab) — OEM
Country of originIndia (made in Ambala, Haryana)

How the Water Is Cooled

Hot water is sprayed through nozzles at the top and trickles down over the mesh packing, which spreads it into thin films and drops with a large surface. Air from the blower enters at the bottom and rises against it. Most of the cooling comes from evaporation: a small part of the water evaporates into the air and takes its latent heat from the rest. This is why the water can leave colder than the air’s dry bulb temperature, approaching but never reaching the wet bulb temperature of the entering air.

Range, Approach and the Energy Balance

The range is the water inlet temperature minus the outlet temperature; the approach is the outlet water temperature minus the wet bulb temperature of the entering air, and range divided by (range + approach) gives the tower effectiveness. The rotameter reading at the inlet minus the measuring tank flow at the outlet gives the water lost to evaporation. For the energy balance, the heat given up by the water is set against the enthalpy gained by the air, found from the orifice air flow and the dry and wet bulb readings at the five stations, which also show how the air warms and moistens on its way up.

Other Cooling Towers and Psychrometry

  • Cooling Tower Test Rig — for the tower characteristic, make-up water flow and psychrometric end states.
  • Acrylic Cooling Tower — table top acrylic working model with induction fan, circulation pump and tank.
  • Psychrometer — wet and dry bulb thermometers with a water reservoir for the wick.

The tower belongs to Thermodynamics Lab, a group within Engineering Lab Equipment.