• +91-85699-09696

Fan Cooled Condenser Manufacturer,Supplier and Exporter in India

Fan Cooled Condenser

Product Code : EL-RACLE-12815
Jlab Export is a leading Fan Cooled Condenser Manufacturer,and suppliers in India

A fan cooled condenser gets rid of the heat from a refrigeration system by blowing room air across its coil. On this unit the fan motor is a permanent split capacitor type, totally enclosed and cooled by the air it moves. It has thermal protection, ball bearings and Class B insulation for 60 °C ambient. Versions are made for 1/6, 1/5, 1/4, 1/3 and 1 hp.

Specifications

Fan motor type Permanent split capacitor (PSC)
Motor enclosure Totally enclosed air over (TEAO)
Motor protection Thermally protected
Insulation Class B, 60 °C ambient
Bearings Ball bearing
Versions For 1/6, 1/5, 1/4, 1/3 and 1 hp
Minimum order quantity 10 units
Dispatch time Usually 4–6 working days
Manufacturer JLab (Jain Laboratory Instruments Pvt Ltd), Ambala, India

Workshop Practice on Condenser Fan Motors

In a refrigeration workshop, students check a PSC fan motor in a fixed order. With the power off, they measure the winding resistance with a Digital Multimeter and look for an open circuit or a short to the motor frame. Next they test the run capacitor on a capacitance meter. A weak capacitor often leaves a PSC motor humming without starting, and students can practise fitting a new run capacitor such as the Capacitors item.

With the motor running, they clamp the supply lead with a Digital Clamp Meter and compare the current with the motor plate. They also confirm that air passes through the coil in the right direction, and check the shaft for bearing noise or end play.

Frequently Asked Questions

What does permanent split capacitor mean?
A PSC motor keeps its start winding and run capacitor in circuit all the time, with no centrifugal switch or start relay. Its starting torque is modest, which is enough for a fan, and it runs smoothly and quietly.

What does totally enclosed air over mean?
The motor case is closed, with no openings for cooling air. Heat is carried away by the air stream from the fan blade passing over the case. The motor should not run for long with the blade off or the airflow blocked.

Why is the motor thermally protected?
A thermal protector inside the motor opens the supply if the windings overheat, for example when the shaft seizes or the coil is clogged with dirt. A motor that keeps tripping needs the cause found, not just a reset.

What does Class B insulation, 60 °C ambient mean?
Class B is a standard insulation class that sets the highest temperature the windings may reach. The 60 °C ambient figure is the hottest surrounding air the motor is meant to work in, which matters in hot plant rooms and outdoor units.

Which version should I choose?
Choose the version marked for the horse power you need, from 1/6 hp up to 1 hp. When replacing a fan motor, also match the voltage, rotation, shaft size and mounting of the old one.

Other Condenser and Evaporator Fans

For a quote, use Add To Cart or send us a message through the contact page.

Last updated: 5 November 2026


   