A recovery machine pumps refrigerant out of a system and into a recovery cylinder, so the circuit can be opened for repair without venting gas. This machine handles refrigerant Categories III, IV and V on 220–240 V, 50 Hz. A 1 or 1.5 hp brushless DC motor drives its oil-less, air-cooled piston compressor.
Specifications
| Refrigerants handled | Categories III, IV and V |
| Power supply | 220–240 V, 50 Hz |
| Motor | 1 or 1.5 hp brushless DC, for high-speed recovery |
| Compressor | Oil-less, air-cooled, piston type, ceramic cylinders |
| Automatic shut-off | At 400–500 psi |
| Display | Digital, large digits, status messages, backlight |
| Protection | Active electronic monitoring |
| Housing | Rubberised, with rail slides |
| Weight | 19 kg or less |
| Operating temperature | 5–40 °C |
| Minimum order quantity | 1 unit |
| Dispatch time | Usually 14–18 working days |
| Manufacturer | JLab (Jain Laboratory Instruments Pvt Ltd), Ambala, India |
Recovery Practicals Before a Repair
Before a trainer is opened to change a filter drier or a valve, students recover its charge. They connect the system ports through the Manifold Gauges for Air Conditioning and run the yellow hose to the machine inlet. The machine outlet goes to one of the Recovery Cylinders, which stands on a Wireless Refrigerant Charging Scale so the class can see the weight going in.
Students run the machine until the low-side gauge shows a slight vacuum, then close the valves and switch off. The weight gained by the cylinder gives the charge recovered, which they compare with the nameplate charge. After the repair they pressure test, evacuate and recharge with the same refrigerant.
Frequently Asked Questions
Which refrigerants can it recover?
It is rated for refrigerant Categories III, IV and V. These groups cover the common CFC, HCFC and HFC refrigerants and blends, from medium-pressure types up to high-pressure blends. For hydrocarbon refrigerants use the Combustible Gas Recovery Machine.
What does the automatic shut-off do?
It stops the compressor when the outlet pressure reaches 400–500 psi. That can happen if a cylinder valve is left shut, the cylinder is too full or it is standing in the sun. Check those points before a restart.
Why is the compressor oil-less?
With no oil in the compressor, no machine oil passes into the recovered refrigerant, and none is carried from one refrigerant to the next. Only the system oil that comes out with the refrigerant has to be dealt with.
Why should the machine be cleared after each job?
Refrigerant left in the compressor, condenser and hoses would mix with the next refrigerant you recover. At the end of each job, recover the vapour left in the machine into the same cylinder, keeping that cylinder inside its marked fill limit. Then close the valves and cap the ports before you change to another refrigerant.